一、設計院本身設計的樓承板的板型和型號,考慮設計院是否同意變更。本鋼結構項目的整個樓板的厚度:如果采用開口和閉口樓承板的話,整個樓板的厚度在110以下,個人建議波高不要超過51mm,因為國家建筑鋼筋混泥土規(guī)范中規(guī)定,鋼筋混泥土中的鋼筋保護層不能低于25mm,樓承板的波高本身有51mm,一般鋼筋的高度大約在20-30mm,鋼筋和樓承板本身也要保持一定的間距,25mm+51mm+(20-30)mm=90-105mm。
1、 Consider whether the design institute agrees to change the type and model of the floor support plate designed by the design institute itself. The thickness of the entire floor slab of this steel structure project: If open and closed floor support plates are used, the thickness of the entire floor slab is below 110. Personally, it is recommended that the wave height should not exceed 51mm, as the national code for building reinforced concrete stipulates that the protective layer of steel bars in reinforced concrete should not be less than 25mm, and the wave height of the floor support plate itself is 51mm. Generally, the height of steel bars is about 20-30mm, and a certain distance should be maintained between the steel bars and the floor support plate itself, 25mm+51mm+(20-30) mm=90-105mm.
二、根據(jù)國家規(guī)范,所以建議110以下的樓板厚度使用波高51mm的樓承板,大于110mm的樓板厚度,可以考慮波高大于51mm的樓承板。次梁的間距,次梁的間距越大,樓承板的波高就要越大,承載力相對要高。
2、 According to national regulations, it is recommended to use a floor support plate with a wave height of 51mm for floor thicknesses below 110. For floor thicknesses greater than 110mm, a floor support plate with a wave height greater than 51mm can be considered. The spacing between secondary beams, the larger the spacing between secondary beams, the higher the wave height of the floor support plate, and the relatively higher the bearing capacity.
樓承板的厚度,樓承板的厚度越大,無支撐跨度就越大。樓承板的鍍鋅基板的屈服強度,屈服強度越大,無支撐跨度就越大。更換板型,在設計院同意的基礎上,考慮變更板型,好是波高一樣,如果是閉口樓承板,替換的板型還是用閉口樓承板,這樣設計院那里也比較容易通過。
The thickness of the floor support plate, the larger the thickness of the floor support plate, the larger the unsupported span. The yield strength of the galvanized substrate of the floor support plate, the larger the yield strength, the larger the unsupported span. To replace the plate type, with the approval of the design institute, consider changing the plate type, preferably with the same wave height. If it is a closed floor support plate, the replacement plate type should still use a closed floor support plate, which will be easier for the design institute to pass.